Description
2 Modes of operation:
– Stand-by operation: Emergency light switches on in case of mains failure
– Maintained operation: Switching over to battery operation in case of mains failure
Automatic monitoring the emergency light fitting acc. to EN 62034. Indication of the test results by 2-colour LED on the light fitting.
Outstanding visibility of the indication sign due to a superb and even illumination of the pictogram.
Stable luminous flux in emergency operation.
TECHNICAL DATA
Marking:
II 3G Ex nR IIC T4 Gc
II 3D Ex tc IIIC T80ºC Dc
Certificate: Declaration of Conformity
Operating conditions: Indoor / Outdoor
Housing: Aluminium, natural finish
Cover: Polycarbonate opalescent white (Pictograms, if required, to be ordered separately)
LED: Linear module 6.500K, CRI > 80, L80 > 50.000h at max. ambient temperature
Battery: Built-in NiMH. A constant trickle charge to the battery ensures readiness of operation at all times.
Recharging time: 24 h
Operating temperature:
-5ºC to 30ºC (maintained operation)
0ºC to 40ºC (standby operation)
Operating frequency: 50/60 Hz
Rated voltage: 220-240 V AC
Ingress protection: IP65
Connection terminals: 3 or 4 poles, clamping range max. 2,5mm2
Cable entries: 1xM20x1,5 plastic cable gland
Additional information
Certified for use in: | Zone 2, Zone 22 |
---|