Description
For lighting of hazardous areas zone 1 and 21, the product series e865 is the perfect choice. It excels with its innovative encapsulated LED modules, the sandwich design of diffuser and reflector to protect the LED modules from mechanical and electrostatic damage, as well as homogeneous illumination and excellent glare limitation because of the frosted diffuser (version “F”).
High-quality LED and electronic control gears guarantee high efficiency and an extremely long service life.
And with the FastFix quick mounting system, installation of the light fittings is easy and saves time.
Housing from glass fibre reinforced polyester.
Clear polycarbonate diffuser.
Aluminium, painted reflector, carrying the encapsulated LED modules and all electrical components, clipped into the cover, removable as a unit.
Looping the cable on one side:
All light fittings of series nD866… have got 2 cable entries on one small side of the housing for cablelooping instead of the through wiring system.
Note: This light fitting is not suitable for application in areas with permanent high humidity in combination with only short periods of operation, such as sewage or stormwater retention tanks or water treatment plants
Option: 4.500K, light colour 845.
TECHNICAL DATA
Marking:
II 2G Ex eb mb q IIC T4 Gb
II 2D Ex tb IIIC T80°C Db
Certificate: EU-Type Examination Certificate
Operating conditions: Indoor / Outdoor
Housing:
Glass fibre reinforced polyester resin
Stainless steel clips (KE), two of them as safety clip (KES), to be opened with screwdriver only
Cover: Injected polycarbonate, frosted (F) or clear, silicone gasket
Closure: Stainless steel clips (KE), two of them as safety clip (KES), to be opened with screwdriver only
Reflector: Sheet Steel, painted, carrying the LED-modules and all electrical components, clipped into the cover, suspendable
LED:
Line modules with clear cover appr. 6,500K, with frosted cover appr.
CRI > 80
L80 > 100.000h at max. ambient temperature | L90 > 85.000h (06L..) at 25°C ambient temperature | L90 > 80.000h (12L..) at 25°C ambient temperature
Operating temperature: -30ºC up to .. see article table
Operating frequency: 0 or 50/60 Hz
Rated voltage: 220/240 VAC. Overvoltage, overload and short circuit protection.
Ingress protection: IP66
Connection: 3 poles up to 4 mm2
Mechanical installation:
Standard: Facing downwards or forwards.
Mounting accessories: see accessories.
Cable entries:
2xM25x1,5 plastic cable gland
1xM25X1,5 plastic plug