Description
Its large dimensions allow a comfortable wiring for a flexible installation.
The use of the brass cable gland M20x1,5 in brass – suitable for armored cables with outer diameters ranging between 13 and 17,5mm – gives the system the capacity to grab armored hoses with sections between 3G1,5 and 5G2,5.
TECHNICAL DATA
Marking:
II 2G Ex e IIC T6 Gb
II 2D Ex tb IIIC T80ºC
Certificate: EU-Type Examination Certificate
Operating temperature: -20ºC to 40ºC
Ingress protection: IP65
Material: Glass fibre reinforced polyester (GRP)
Nominal isolation voltage: 690 V
Rated voltage: 400 V | 400 V | 110 V | 24 V
Utilization categories: AC-12 | AC-15 | DC-13 | DC-13
Current ranges: 16 A | 10 A | 0,5 A | 1 A
Conventional thermal current: 16 A/ 40 ºC, 11 A/ 60 ºC
Electrical connection: Terminals 2,5 mm2
Duty cycle: 10^6 commutations
Additional information
Certified for use in: | Zone 1, Zone 21 |
---|