RedBin-P ATEX Pressure / Differential Pressure Switch
Description
Highest protection class (ATEX) and IP66 protection, small dimensions, universal functions and technical data guarantee safe operation even under difficult environmental conditions. All sensors are programmable on site without any additional tools.
– Power supply 24 VAC/DC
– Potential free switching contact output
– Adjustable switching threshold, hysteresis and start-up bypass time
– Adjustable switch activation delay (acc. to type)
– Integrated Ex-e terminal box
– No addional Ex-i module required
– No intrinsically safe wiring/installation between panel and sensor required
– No intrinsically safe wiring/installation and no space in the panel required
– Optional second switching output (acc. to type)
– Display with backlight, can be switched off
– Password locking
– Compact design and small dimension
All pressure switches require a 24 VAC/DC power supply. The electrical wiring must be realized via the integrated Ex terminal box acc. to ATEX.
TECHNICAL DATA
Marking:
II 3(1)G Ex nC [ia Ga] IIC T6…T4 Gc
II 3(1)D Ex tc [ia Da] IIIC T80°C…T130°C Dc IP66
Certificate: EU-Type Examination Certificate
Supply voltage / frequency: 24 VAC/DC ± 20% (19,2…28,8 VAC/DC), 50/60 Hz
Current power consumption: 150 mA, ~ 4 W, internal fuse 500 mAT, without bracket, not removable
Galvanic isolation: Supply for relay output min. 1,5 kV
Electrical connection: Terminals 0,14…2,5 mm² at integrated Ex-e terminal box, stripping lenght 9 mm, torque 0,4…0,5 Nm, equipotential bonding 4 mm²
Display / Control elements: LC-Display, backlit, for configuration, user guidance, parameter and actual value indication. Status indicator via LEDs / 3 buttons for configuration
Sensor / Sensor circuit: Piezo messure transmitter / Internal intrinsically safe (IS) circuit
Housing: Aluminium housing T6 (T80 °C) at −20…+50 °C
Ambient Temperature – Humidity: -20…+50 °C (storage temperature -35…+70 °C) / 0…95 % rH, non condensing
Pressure connection: P+ / P- sleeves Ø 4…6 mm
Measuring range: 0…100 Pa | 0…500 Pa | 0…5000 Pa.
Minimum measuring range is 5 % of full range (e.g. 25 Pa at …500 Pa switch)
Response time of sensor: T90 / 5 s
Accuracy of pressure: < ± 1 % typically, max. ±2 % of end value ± 1 Pa
Setting zero point: Via menu. Short-circuit mechanically both tube connectors P+ / P− for the moment of zero point setting
Setting range hysteresis: 0,1…10 Pa (factory setting 2 Pa) | 0,5…50 Pa (factory setting 10 Pa) | 5…500 Pa (factory setting 100 Pa)
Start delay: 5 s
Start-up bypass time (AUB): 3…240 s (factory setting 120 s)
Switch activation delay: 0…240 s (factory setting 0 s / Off) | – | –
Output: Potential free switching contact – breaking/making contact, adjustable per menu
Max. rating load: 0,5 A (30 VAC/DC) – 0,1 A (250 VAC) – 0,1 A (220 VDC); min. rating load: 10 mW / 0,1 V / 1 mA
Additional relay output (type …-2): – | as above | –
Duration of life:
Mechanical: 10 x 106
Electrical: (rated load) 100 x 103
Scope of delivery: Pressure switch, 3 self-tapping screws 4,2 x 13 mm resp. in stainless steel (with …CT and …VA versions), short circuit tube
Dimensions: 180 x 107 x 66 mm
Weight: ~ 950 g
Cable entries: 2 x M16x1,5, Ex-e plastic cable gland ~ Ø 5…9 mm
Additional information
Certified for use in: | Zone 2, Zone 22 |
---|