Description
Highest protection class (ATEX) and IP66 protection, small dimensions, universal functions and technical data guarantee safe operation even under difficult environmental conditions.
All frost protection thermostats are programmable on site without any additional tools. The switching point is scalable within the maximum ranges.
– No addional Ex-i module required
– Integrated Ex-e terminal box
– Power supply 24 VAC/DC
– LED switching state indication
– Compact design and small dimension
– IP66 protection
TECHNICAL DATA
Marking:
II 3(1)G Ex nC [ia Ga] IIC T6 Gc
II 3(1)D Ex tc [ia Da] IIIC T80°C Dc IP66
Certificate: EU-Type Examination Certificate
Supply voltage / frequency: 24 VAC/DC ± 20% (19,2…28,8 VAC/DC), 50/60 Hz
Current, power consumption: 150 mA, ~ 4 W, internal fuse 500 mAT, not removable
Galvanic isolation: Supply for relay output min. 1,5 kV
Electrical connection: Terminals 0,14…2,5 mm² at integrated Ex-e terminal box, stripping length 9 mm, torque 0,4…0,5 Nm, equipotential bonding 4 mm²
Control elements: Rotary control for setpoint adjustment and fixing screw
Measuring range: Setpoint adjustable −10 °C…+15 °C
Status indication: Via LEDs – GREEN: ambient temperature is above setpoint (normal), RED: ambient temperature is below setpoin
Housing material: Aluminium die-cast housing, coated.
Ambient temperature: −20…+50 °C, capillary max. +80 °C, storage temperature −35…+70 °C
Temperature class: T6 (T80 °C) bei −20…+50 °C
Ambient humidity: 0…95 % rH, non condensin
Sensor circuit: Internal intrinsically safe (IS) circuit
Capillary: Lenght: …FR-3 – 3 m ±15 cm | …FR-6 – 6 m ±20 cm, min. active length ~ 40 cm | min. bending radius 2 cm
Hysteresis: ~ 6 K, accurancy of setpoints ± 3 K
Start delay: 5 s
Output:
Potential free switching contact – breaking contact
max. rating load – 0,5 A (30 VAC/ DC) – 0,1 A (250 VAC) – 0,1 A (220 VDC)
min. rating load – 10 mW / 0,1 V / 1 mA
Duration of life:
Mechanical 10 × 106
Electrical (rated load) 100 × 103
Scope of delivery: Frost protection thermostat, self-tapping screws 4,2 x 13 mm
Dimensions: 180 × 107 × 66 mm (without connectors)
Weight: ~ 950 g
Cable entries: 2 x M16x1,5 mm, Ex-e approved, for cable diameter ~ Ø 5…9 mm
Additional information
Certified for use in: | Zone 1, Zone 21 |
---|