Description
Each block is operated by means of a robust and reliable non-lockable handle.
In this particular case we present a head-end and four services consisting of:
1x 2x32A Miniature Circuit Breaker (SCH iC60L A9F94232) -> As a head-end.
4x Blocks (Residual Current Circuit Breaker + Miniature Circuit Breaker / SCH A9F94216 + A9Q41225) -> As services. Each block is associated with a handle
Other protection sizes are possible on request.
TECHNICAL DATA
Marking:
II 2G Ex db IIB+H2 T6 Gb
II 2D Ex tb IIIC T85°C Db IP66
Certificate: EU-Type Examination Certificate
Material: Aluminium, Grey RAL 7000
Operating temperature: -20ºC to +40ºC
Ingress protection: IP66
Dimensions:
External: 400x500x250 mm
Internal: 305x405x202 mm
Interior: Mounting Plate 290x390mm
Content:
1x 2x32A Miniature Circuit Breaker (SCH iC60L A9F94232) -> As a head-end.
4x Blocks (Residual Current Circuit Breaker + Miniature Circuit Breaker / SCH A9F94216 + A9Q41225)
-> As services. Each block is associated with a handle
Cable entries: 5x M20X1,5 (cable glands/plugs not included)