Explosion-proof emergency light fitting with individual battery set.
End of life swiching-off system (EOL).
Automatic monitoring battery life.
Función de test manual.
Central locking system with detachable cover for easy lamp replacement.
Mode maintained: Switching over to battery operation in case of mains failure.
Mode Stand by: emergency operation in case of mains failure.

Can be used in:
Zones 1, 2, 21, 22.

Explosion protection:
II 2 G Ex deq IIC T4 Gb
II 2 D Ex t IIIC T80ºC Db

Certificates: PTB 07 ATEX 2031, 2040

Ambient temperature: Indoors / Outdoors

Enclosure: Glass fibre reinforced polyester

Diffuser: Polycarbonate with internal prisms

Lamp holder: T 26 / T 38

Charging time: 24 h

Ambient temperature: -20ºC to +55ºC (nominal range: 0ºC to +40ºC)

Range frequency: 50/60 Hz

Range voltage: 220/254 VAC (+-10%)

Ingress protection: IP 66

Cable entries: 1xM25x1,5 cable gland (plastic) / 1xM25x1,5 plug (plastic)